Jeff Hebenstreit - UL 12/4/2013
2
Background Standard was revised: Evaluation of Sodium Hypochlorite for Chlorate SPAC = 200 ppb UL began evaluating samples for chlorate in 2013 Many manufacturers having difficulty meeting the SPAC at the current Maximum Use Level (MUL) MUL based on 10 mg/L FAC
3
Some Chlorate Factors Concentration of bleach Storage temperature Storage time Other factors
4
Chlorate SPAC Currently SPAC = 200 ppb Ballot passed Joint Committee to revise Would have changed SPAC to 300 ppb NSF Council of Public Health Consultants Failed to pass Rounding rules have since passed ballot
5
Data Summary FAC Dose10 mg/L2 mg/L Factory Locations35 Mean (ug/L)670133 Max (ug/L)1500300 Min (ug/L)9218 # samples </=200 ppb SPAC228 # samples </=300 ppb SPAC735
6
Revision to MUL NSF 60 allows for decreased MUL Floor of 2 mg/L FAC Is this a usable product certification?
7
Considerations Review the 2 mg/L FAC Dose Is this adequate for end users Determine the need to re-ballot the SPAC Changes to rounding rules Determine the need for a longer implementation period Nature of changes may require increased time