Download presentation
1
Intelligent Control Panel SLC
SLC Manual
2
NFPA Style 4 SLC FACP Note Branch Taps Note Maximum Distance
Branch Line Resistor from End of Line to FACP Shall Not Over 50 ohms per Branch Note Branch Taps Note Maximum Distance 12, Ohms Twisted Pair only Twisted Unshielded Pair 12 to 18 AWG SLC Distance 12 AWG 3180 M AWG M 14 AWG 2438 M AWG M SLC Manual
3
Style 4 with Isolators FACP
M Note: Isolators provide survivability in event of branch short Ensure proper Isolator loading SLC Manual
4
NFPA Style 6 SLC Loop Resistor from End of Line to FACP
Shall Not Over 50 ohms M M M M Note Maximum Distance 12, ohms Twisted Pair M M SLC Manual
5
Style 6 with Isolators M M M SLC address capacity of loop is reduced by 2 addresses for every isolator device in excess of 200. M M M M Note Isolators provide survivability in event of short on segment Ensure proper Isolator loading M M SLC Manual
6
Style 7 ISO M C SLC address capacity of loop is reduced by 2 addresses for every isolator device in excess of 200. Each device must be individually isolated for this mode Ensure proper Loop Loading SLC Manual
7
SLC Performance Discuss Wiring performance SLC Manual
8
Floating Shield (+) SLC Channel A no connection (-) SLC Channel A NFS-640 In retrofit, disconnect shield drain wires at devices and junction boxes Shield increases wiring capacitance, reducing overall distance SLC Manual
9
SLC Data Formats CLIP Flash
Each device individually polled and responds with measured pulse width Default setting in Auto Programming Flash Devices polled in blocks of 10 Each device responds with true digital signal. CLIP only devices will give invalid reply in Flash Mode FlashScan is an algorithm that greatly enhances the speed of communication between the Analog intelligent devices. If one of the devices within a single group has new information, The panel CPU stops the group poll and concentrates on single points. The net effect is a response speed greater than five times that of earlier designs. SLC Manual
12
LED Operation SLC Manual
13
FlashScan Modules 9 8 1 7 2 6 3 5 4 Break-off address stop
1 2 3 4 7 6 5 ADDRESS LOOP ONES 10 11 12 13 14 15 TENS Break-off address stop for panels with FlashScan Mode. SLC Manual
14
FZM-1 接點3、4需接可復歸( Resettable) DC 24電源接線採用Class B時,終端電阻為3.9KΩ
15
FZM-1 接線採用Class A時,終端電阻為3.9KΩ
16
FMM-1 接線採用Class B時,終端電阻為47 KΩ、1/2W
17
FMM-1 接線採用Class A 時,無需終端電阻
18
FMM-101 終端電阻為47 KΩ、1/2W
19
FCM-1 輸出接線採用Class B時 接點6、7之終端電阻為47KΩ、1/2W
20
FCM-1 採用Class A 時,無需終端電阻
21
FRM-1 外接負載應小於模組之接點容量 接 點 容 量 電阻性元件 30VDC @ 2A
電感性元件 1A 交流元件 0.5A
22
Devices - Modules Isolator Module (ISO-X)
Supervises loop wiring for short circuit conditions Allows critical component functions Required for Style 7 operation Supported by FlashScan and CLIP systems 1 2 3 4 Loading 25 Units per Isolator All detectors except for Multi/Acclimate 1 Unit Multi/Acclimate detectors 12 Units Standard Bases 0 Units Sounder/Relay Bases 2.5 Units FMM, FZM, FCM, FRM Modules 1 Unit FDM 2 Units XP5 Modules 5 Units XPP, XPIQ 1 Unit Up to 100 Isolators per Loop without loss of devices Each Isolator over 100 reduces loop capacity by 2 devices. SLC Manual
23
FDM-1 Wiring Class B 8 9 1 2 3 4 7 6 5 ADDRESS LOOP ONES 10 11 12 13 14 15 TENS The circuit connected to terminals 6 & 7 are assigned the base address. The circuit connected to terminals 8 & 9 are assigned the base address plus 1. RED LED lights for either circuit 1 or circuit 2 alarm. SLC Manual
24
FCM-1 Control Modules Control Module Relay Module
FCM-1 Class A or B NAC, Speaker or Telephone 30VDC 25 Vrms Vrms 40 Ohm telephone riser Relay Module FRM-1 Dual Form-C operation (DPDT) 8 9 1 2 3 4 7 6 5 ADDRESS LOOP ONES 10 11 12 13 14 15 TENS SLC Manual
25
FRM-1 Contact Rating SLC Manual
26
Devices - Modules Isolator Module (ISO-X)
Supervises loop wiring for short circuit conditions Allows critical component functions Required for Style 7 operation Supported by FlashScan and CLIP systems 1 2 3 4 Loading 25 Units per Isolator All detectors except for Multi/Acclimate 1 Unit Multi/Acclimate detectors 12 Units Standard Bases 0 Units Sounder/Relay Bases 2.5 Units FMM, FZM, FCM, FRM Modules 1 Unit FDM 2 Units XP5 Modules 5 Units XPP, XPIQ 1 Unit Up to 100 Isolators per Loop without loss of devices Each Isolator over 100 reduces loop capacity by 2 devices. SLC Manual
27
Wiring the B224BI Isolator Base
Twisted Pair Recommended Listed FACP Isolator bases prevent an entire communication loop from being disabled when a short circuit occurs, by isolating that part from the remainder of the circuits. OTHER INTELLIGENT DEVICES SLC Manual
28
Wiring the B710HD Base AUX POWER SUPPLY SLC SLC Manual
29
Wiring an NBG-12LX Pull Station
+ SLC - + SLC - SLC Manual
30
Wiring Surge Suppressor
Building 2 Building 1 P = Primary S= Secondary UL requirement for a PRIMARY surge suppressor at the exit & entrance points. Recommend SECONDARY at FACP SLC Manual
31
Any Questions? SLC Manual
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.