FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps.

Similar presentations


Presentation on theme: "FIREPOWER BY SABURKE. Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps."— Presentation transcript:

1 FIREPOWER BY SABURKE

2 Distributed Power Modules Model 5495Model 5499 6 Amps9 Amps

3 3 Amps per output 4 Notification outputs 1 Aux output Fuseless Design Dip switch programmable Distributed Power Modules

4 Fully Supervised Flexible wiring (Class A or Class B) 2 Input circuits (Activated and supervised by FACP)

5 Synchronization Built-in for appliances from System Sensor, Gentex, Faraday or Wheelock.. Distributed Power Modules

6 SWITCHING v.s. LINEAR DESIGN -Up to 50% more efficient. -Puts out less damaging heat. -Faster input re-action. -Gives you lighter weight. LOWER SHIPPING COSTS!! - Switching power supply’s are used in computers. Distributed Power Modules

7 Signal Input Terminals Class B wiring from a FACP The fire panel supervises its notification output the same way it supervises ordinary notification circuits (open circuit = trouble). The power supplies emulates the trouble behavior by breaking the EOL supervision current for any power supply trouble, putting the fire panel into a notification circuit trouble.

8 The power supplies will accurately sense the polarity of the fire panel’s notification circuit to drive the outputs whether or not the supervision connection is intact. During the Alarm Condition (ON) the fire panel will not sense trouble conditions though its notification circuits. Signal Input Terminals Class B wiring from a FACP Alarm Condition (ON)

9 CURRENT REQUIREMENTS (Battery Calculations) 1.) Current Draw From Host Fire Panel = 15mA 2.) Current Draw From Batteries = ?

10 Only the green AC LED should be on in a normal condition. 5495 Board

11 Only the green AC LED should be on in a normal condition. 5499 Board

12 Trouble Relay The Trouble Relay is one option to signal the trouble condition to the FACP, the primary way is though the FACP Notification circuit connected to the input.

13 Notification Power Class A wiring from a FACP

14 Notification Power Class B wiring from a FACP Input 1 will short terminal 19 to terminal 17 during normal operation, and open during trouble conditions. Same operation if using input 2 (terminals 14 and 16).

15 Notification Power Extend Class B Circuit Notification devices powered from the main fire panel. The EOL must be the only thing connected to terminals 17 and 14!

16 DIP Switch Settings

17 DIP Switch Settings ANSI Temporal Output

18 DIP Switch Settings

19 DIP Switch Settings / Sync.

20

21 DIP Switch Settings

22 Notification Power Class B wiring from a FACP

23

24

25 Stand Alone Operation More Power What’s the max. current that the Model 5495 can supply with 4 the outputs? What’s the max. current that the Model 5499 can supply with 4 the outputs?

26 Stand Alone Door Holder Operation FACP 5495 or 5499 Normally Closed Alarm Relay What’s the max. current that the Aux. Power output can supply???