Presentation is loading. Please wait.

Presentation is loading. Please wait.

UT cooling discussion 3 december 2014

Similar presentations


Presentation on theme: "UT cooling discussion 3 december 2014"— Presentation transcript:

1 UT cooling discussion 3 december 2014
Bart Verlaat

2 System summary Standard:
TABLE 1. PARAMETERS OF THE UT COOLING SYSTEM Property Value Units Comments GENERAL Cooling system 2-PACL Cooling power 5000 W total plus margin (see est. Table 3) Fluid CO2 Fluid filtration need accessible, replaceable in technical stop Emergency redundancy Temporary share with VELO system UPS connection want entire system, minimally controls Component design pressure, max 100 bar max pressure Component test pressure, max 150 max pressure = 1.5*Pvap(CO2) DT_evap on stave 0.5 °C stability OPERATIONAL MODES T_evap, nominal, data-taking, cold -40 to -20 max power 5 kW T_evap, standby, cold From 1 to 2 kW T_evap, beam pipe bake-out Amb temp Cooling off T_evap, installation mode, cold 0.5 kW-1 kW (1 half-plane operating) DISTRIBUTION AND MANIFOLD Number of individual loops 68 one loop per stave Control of loops TBD remote ot local ON/OFF control (?) Manifold in BOX local, in UT BOX, connected to loops Connection to manifold flexible needs to move with UT as it retracts CONTROL Continuous T_evap control remotely controlled by 2PACL design T_evap Set point common (?), range (?) T_evap Monitoring stave input all stave inputs, plus module T readback Plant to DSS output signals ? no idea what this means ! Env. gas to DSS output signals DSS to plant input signals ENVIRONMENTAL GAS Gas dry N2, Air gas in UT BOX max dew point safety several over-pressure valves at strategic points Standard: MDP=110 bar (for large volumes = safety valves) MDP=130 bar (for small volumes = burstdisc) Test pressure: 1.43x => 157 bar or 186 bar. If a 2 PACL is designed for -40’C all other temperatures can easily be selected above up to 20’C Not clear what this means and why it is considered

3 PED Classification (1) (Pressure Equipment Directive)
PED classification for CO2 systems. Stored energy = MDP x Volume MDP = Relieve pressure MDP= TenvMax or P+dPpump)x110% PTP = 1.43 x MDP MDP = Maximum design pressure, PTP = Proof Test Pressure Stored energy of accumulator in case of fluid storage (worst case). Find minimum for stored energy (Not necessarily at lowest pressure)

4 PED Classification (2) Category Design Fabrication Commis-sioning PED Module Applicable to MDP=110bar Art. 3.3 Good practice V≤0.45 Liter Dn≤ø32 mm I A 0.45<V≤1.8 L DN≤ø100mm II Notified Body control A+A1 1.8<V≤9.1 L DN≤ø250mm III Approved fabrication procedure B1+F 9.1<V≤27.2L DN>ø250mm IV G V>27.2L The higher the PED class, the larger notified body involvement

5 Trapped liquid Trapped cold liquid is a real danger in a cooling system. Be careful with introducing too many valves Don’t use valves with dead volumes Every volume needs a relieve AMS-TTCS has no valves, only liquid trap possible in frozen condenser MDP=3000 bar for condenser! LHCb-VTCS and Atlas IBL have burst discs at each volume or relieve valves. + controlled valves to avoid liquid trap MDP=130 bar (Swagelok burst disc) Ball valve with T-hole

6 System summary Standard:
TABLE 1. PARAMETERS OF THE UT COOLING SYSTEM Property Value Units Comments GENERAL Cooling system 2-PACL Cooling power 5000 W total plus margin (see est. Table 3) Fluid CO2 Fluid filtration need accessible, replaceable in technical stop Emergency redundancy Temporary share with VELO system UPS connection want entire system, minimally controls Component design pressure, max 100 bar max pressure Component test pressure, max 150 max pressure = 1.5*Pvap(CO2) DT_evap on stave 0.5 °C stability OPERATIONAL MODES T_evap, nominal, data-taking, cold -40 to -20 max power 5 kW T_evap, standby, cold From 1 to 2 kW T_evap, beam pipe bake-out Amb temp Cooling off T_evap, installation mode, cold 0.5 kW-1 kW (1 half-plane operating) DISTRIBUTION AND MANIFOLD Number of individual loops 68 one loop per stave Control of loops TBD remote ot local ON/OFF control (?) Manifold in BOX local, in UT BOX, connected to loops Connection to manifold flexible needs to move with UT as it retracts CONTROL Continuous T_evap control remotely controlled by 2PACL design T_evap Set point common (?), range (?) T_evap Monitoring stave input all stave inputs, plus module T readback Plant to DSS output signals ? no idea what this means ! Env. gas to DSS output signals DSS to plant input signals ENVIRONMENTAL GAS Gas dry N2, Air gas in UT BOX max dew point safety several over-pressure valves at strategic points Standard: MDP=110 bar (for large volumes = safety valves) MDP=130 bar (for small volumes = burstdisc) Test pressure: 1.43x => 157 bar or 186 bar. If a 2 PACL is designed for -40’C all other temperatures can easily be selected above up to 20’C Not clear what this means and why it is considered

7 2PACL temperature freedom
IBL set-point tests All temperature levels can be selected Today Detector off Detector on As long as sub cooling level is sufficient (>10’C) CO2 liquid in plant

8 Power requirements Is depending on temperature, so better to give the T0 and I0 values What about the electronics? Purpose not understood

9 More modes…

10 Thermal chain in detectors
The design of the cooling is the whole chain between heat source and heat sink Typical example for IBL Heatload Th. paste Glue Glue HTC ΔP CO2 in tube Silicon CF-sheet C-foam Pipe wall Manifold

11 Thermal chain in detectors
The design of the cooling is the whole chain between heat source and heat sink Typical example for IBL Heatload Th. paste Glue Glue HTC ΔP CO2 in tube Silicon CF-sheet C-foam Pipe wall Manifold Load variations give gradients w.r.t the common sink => Outlet manifold!

12 Design of cooling: From source to sink
So the reference should not be at a pipe wall, nor at the liquid temperature as it is generally approached. This is similar then taking a reference in the middle of the structure. Loaded stave temperature: -24.4°C (0.72 W/cm2) Stave conductance ~61% Atlas IBL example Heat transfer ~ 19% Unloaded stave temperature: -39°C Pressure drop ~20% Inlet manifold Outlet Manifold = temperature reference

13 First we need to understand what happens inside a cooling tube
First we need to understand what happens inside a cooling tube? Heating a flow from liquid to gas

14 Cooling method used in detector cooling:
The 2-Phase Accumulator Controlled Loop (2PACL) 2-Phase Accumulator Shielding wall P7 Evaporator inside detector (4-5) Heat in Long distance (50-100m) P4-5 HFC Chiller 5 Condenser 6 Detector heat 2 3 1 Capillaries (3-4) for flow distribution Pump Transfer line (Heat exchanger) 4 2PACL principle ideal for detector cooling: Liquid overflow => no mass flow control and good heat transfer No local evaporator control, evaporator is passive in detector. System not sensitive for heat load changes Very stable evaporator temperature control at a distance (P4-5 ≈ P7) Large operational temperature range (+20’C to -40’C)

15 Understanding detector evaporator tubes
Outlet manifold: Pressure = fixed Inlet manifold: Temperature = fixed In a 2PACL the capillary inlet temperature is a function of the outlet saturation pressure. The detector inlet is close to saturation. But can be liquid due to pressure drop Usually ambient heating is enough to overcome sub cooled entry state Detectors with high dP have to be designed to cope with liquid at the inlet FE: pre heating by electronics (CMS pixel) Pressure drop of the evaporator tube and outlet tube is part of the thermal resistance chain from heat source to sink! Inlet manifold Inlet capillary dP Detector dP Outlet line dP outlet manifold Temperature exchange

16 Long branch thermal profile
Liquid 2-Phase Inlet tube Evaporator tube Outlet tube HTC Temperature gradient inside detector due to pressure drop and heat transfer dP Offset of evaporator temperature due to outlet pressure drop Liquid entry into evaporator Manifold temperature = common reference of all branches Inlet: 2mm x 4m, Detector: 2mm x 4m, Outlet: 2mm x 4m Heatload on detector: 200 Watt

17 Flow distribution: Inlet tube reduction
Which flow do we need when 200 Watt to a single stave is applied? Inlet: 2mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Pressure drop and dry-out calculated using CoBra Pumping energy is flow x dP. Adding capillaries can save pumping power (in example 1.61*3.54/2.18*3.75=0.70 => 30% saving) Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012

18 Influence of the in and outlet-lines on thermal performance
Inlet: 2mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 2mm x 4m Inlet: 1mm x 4m Stave: 2mm x 4m Outlet: 3mm x 4m Figures from: DESIGN CONSIDERATIONS OF LONG LENGTH EVAPORATIVE CO2 COOLING LINES Bart Verlaat and Joao Noite, GL-209, 10th IIF/IIR Gustav Lorentzen Conference on Natural Working Fluids, Delft, The Netherlands 2012

19 Dealing with environmental heat pick-up
Three important statements: Expose return tube to ambient heating There is usually enough cooling power left Connect as much as possible the inlet to the outlet Outlet boils first (lower P), so will take care of heat absorption Avoid boiling before the inlet manifold Flow separation will feed some channels with vapor only! Capillary dP makes manifold liquid Pre capillary heat pickup Inlet manifold outlet manifold Manifold boiling Outlet transfer line outlet manifold Outlet transfer line Remaining cooling power for ambient To keep this problem simple: Have the manifold right after the heat exchanging transfer line.

20 IBL: A detector with very long in and outlet lines
The IBL detector is only 800mm long, but has about 15m long in and outlets. dT due outlet line pressure drop significantly (ca 3ºC) Ambient heat load in same order as detector load Atlas IBL example Inlet Outlet 2 12 Heat exchange Ambient Ambient heating 9 4 6 7 IBL


Download ppt "UT cooling discussion 3 december 2014"

Similar presentations


Ads by Google