TMALL 0141 Presentation v 1.0 A concept for simplified Fixed Fire Fighting System: Northern link, Stockholm Ulf Lundström, TSO Swedish Transport Administration
2
2
3
3
4
4 Northern Link: Part of ring road project 3,5 km long, in all 15 km of tunnels
5
5
6
6 Basic fire safety concept: Free flow traffic
7
7
8
8 Fresh air
9
9 2004: Southern Link opens for traffic: 100 000 vehicles /day, estimated 60 000. = Slow traffic
10
10 2004-2012: The tunnel closing when cogestion occurs.
11
11 2009 The safety concept of the Northen Link is uppdated in four aspects: Improved detection Improved traffic controll and management Improved message handling to users Fixed Fire Fighting System
12
12 Fixed Fire Fighting System in the Northern Link: Safety, not asset protection No traditional tunnel sprinkler Focus on cost effectivenes, robustnes and mantainability
13
13 Design solutions: Long sections (75 m) Low pressure, large droplets Extended coverage nozzles City water supply, no pumps Remtotely operated membrane valves Starts automatically at 90 C in heatdetection cable Protected against corrosion and freezing
14
14 FFFS in the project Northern link
15
15
16
16
17
17
18
18
19
19
20
20
21
21
22
22
23
23
24
24
25
25 General data: Number of sections: 230 Total length: ca 15 km Investment cost: 72 Msek (7 M€) Investment cost per km: 5 Msek (0,5 M€) Experiences since nov 2014: No fires No false activations 100% availability 100% reliability (test once a year) No service or repairs required
26
26 Tests conducted in cooperation with SP Water distribution tests at different air speeds Visibility in a activated section Visibility from a moving car in a activated section Test of evacuation by foot through a activated section Fire tests: risk of fire spread between vehicles, 6 MW propan flame Activation in winter conditions (- 6 grader C)