Download presentation
Presentation is loading. Please wait.
Published byOwen Farmer Modified over 9 years ago
1
The Product Range Ionisation smoke detector Optical smoke detector Heat detector Multisensor detector Manual call Device
2
Discovery Features Drift compensation for smoke detectors Full R-o-R processing for heat detector Multi-mode operation Transient rejection Flashing LED Self-test
3
Self-test Based on proven methods used in XP95 range On-board processor controls and evaluates test Available on all detectors using standard XP95 command bit
4
Flashing LED Option Selectable as an option via the engineer’s setup menu LEDs flash when polled
5
Drift Compensation Monitors long-term drift Maintains clean air value close to 25 Adjusts levels to maintain sensitivity Operates in all modes Independent of protocol Transparent to control panel
6
Compensation in Action Time (hours) Analogue value Raw analogue value Compensated analogue value 55 25 Alarm threshold Fire outbreak
7
Compensation Limit Time (months) Analogue value Raw analogue value Compensated analogue value 55 25 Alarm threshold Limit of compensation
8
Normalisation Time (hours) Analogue value Raw analogue value Compensated analogue value 55 25 Alarm threshold Normalisation (Rapid update)
9
25 55 Analogue Value Smoke Level Clean air Alarm level Mode 5 Mode 1 Mode Comparisons
10
Benefits of Multisensor Smoke-only mode Heat-only mode Multisensor modes give uniform response to broad range of fire types High sensitivity available
11
Multisensor Modes
12
Heat Detector Modes
13
The Best Detector for the Job?