Download presentation
Presentation is loading. Please wait.
Published byAron Homer Johns Modified over 9 years ago
1
Frankfurt (Germany), 6-9 June 2011 Irina Melnik – the Netherlands – Session S2 – 0665 Intelligent Distribution Substation improves power quality
2
Frankfurt (Germany), 6-9 June 2011 Need for new technologies Monitoring and control New technologies Changes in power flows Larger voltage variations Uncertainty for planning Complex grid operation Fluctuating loads Distributed generation MV LV Load Power MV LV Load Power
3
Frankfurt (Germany), 6-9 June 2011 Intelligent distribution substation (IntDS) Additional functions of the IntDS: Monitoring Control Improving Power Quality Developed by a consortium of Dutch industries Installed and tested in the grid of DSO Alliander
4
Frankfurt (Germany), 6-9 June 2011 “Intelligent” components of IntDS Electricity storage system with bidirectional inverter Measurement system Smart Transformer
5
Frankfurt (Germany), 6-9 June 2011 IntDS implementation District with large amount of micro Combined Heat Power at customers
6
Frankfurt (Germany), 6-9 June 2011 Test program Voltage control Reduction of harmonic distortion Reduction of flicker Mitigation of voltage dips Power Quality improvement by the IntDS:
7
Frankfurt (Germany), 6-9 June 2011 Voltage control Performed by Smart Transformer: Electronic tap changer ensures a constant voltage level on the LV rail of the IntDS. The voltage control set-point has to be determined to achieve the optimal voltage level on PCC’s of all LV customers. Smart Transformer
8
Frankfurt (Germany), 6-9 June 2011 Voltage control – test results U avg U max U min LV bus-bar 1 2 3 control no control LV customer 1 2 3 control no control
9
Frankfurt (Germany), 6-9 June 2011 Harmonic distortion reduction Performed by ESI (Electricity storage inverter) : Resistive harmonic damping Passive harmonic damping The filter capacitors of the ESI take part in the filtering of harmonics. Electricity storage system with bidirectional inverter
10
Frankfurt (Germany), 6-9 June 2011 Harmonic distortion reduction – test results H03 max H05 max H07 max THD max LV bus-bar control no no control LV customer controlno control no
11
Frankfurt (Germany), 6-9 June 2011 Voltage dips mitigation Can be performed by: the Smart Transformer the ESI (Electricity storage inverter) Voltage dips occur only a few times per year on an LV bus-bar of Dutch distribution substations. That’s why this functionality is not actively tested.
12
Frankfurt (Germany), 6-9 June 2011 Flicker reduction (LV side) Performed by: The electronic tap changer of the Smart Transformer The flicker reduction control of the bidirectional inverter (ESI) of the storage system.
13
Frankfurt (Germany), 6-9 June 2011 Flicker reduction – test results Plt avg Pst avg Plt max Pst max LV bus-bar no control LV customer no control
14
Frankfurt (Germany), 6-9 June 2011 Conclusions The Intelligent substation has proved to be safe in operation. The first field test results demonstrate a significant reduction of voltage variations, harmonic and THD levels both at the LV bus-bar of the IntDS and at the LV customers. Further metering and test programs will be performed to set optimal set-points for control equipments. The proved principles can be used for area’s with high levels of PQ distortions. Irina Melnik – the Netherlands – Session S2 – 0665
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.