ME444 ENGINEERING PIPING SYSTEM DESIGN CHAPTER 1: INTRODUCTION
2
TENTATIVE SCHEDULE BEFORE MIDTERM: THEORY OF FLOW IN PIPE, PIPE SIZING, PIPING MATERIALS, PUMP SELECTION AFTER MIDTERM: DESIGN OF VARIOUS PIPING SYSTEMS FOR BUILDINGS AND INDUSTRIES Book: dulyachot.me.engr.tu.ac.th/pipebook.pdf
3
CONTENTS 1.INTRODUCTION 2.STANDARDS 3.BASIC UNITS 4.BASIC FLOW IN PIPE 5.QUICK LOOK AT PIPE DRAWINGS
4
1. INTRODUCTION PIPING SYSTEMS EXIST IN EVERY ENGINEERING APPLICATION. APPLICATIONS: PLUMBING, FIRE PROTECTION, PROCESS, AIR-CONDITIONING, REFRIGERATION, VENTILATION, COMPRESSED GAS, STEAM FUNCTION: TRANSMIT FLUID AT A PREFERED RATE TO THE DESTINATIONS WITH PREFERRED PROPERTIES (I.E. PRESSURE, TEMPERATURE) SESSION 1 MAIN REFERENCE: PUMPING STATION DESIGN
6
DESIGN CONCEPT SOURCEPIPING SYSTEMEND USERS
7
PIPING SYSTEM DESIGN END USERS’ REQUIREMENTS SOURCE PIPING SYSTEM PUMP MATERIAL TYPE SIZE PIPE MATERIAL THICKNESS PATHS SIZES VALVE & ACC. PRESSURE TEMPERATURE … FLOW PRESSURE TEMPERATURE …
8
2. STANDARDS
9
ASME STANDARDS
10
STANDARDS
12
British Standard Deutsches Institut für Normung Japanese Industrial Standard Old mark (expired)
13
3. BASIC UNITS PIPE SIZE: INCHES, mm. PIPE LENGTH: FEET, METRES VOLUME: CU.M., CU.FT., LITRES, GALLONS FLOWRATE: GPM, CU.M./H, LPS, LPM, CFM PRESSURE: PSI, BAR, m.WG., KG/CM 2 POWER: KW, HP STUDENTS MUST HAVE THE CONVERSION FACTORS
14
7 basic quantities
15
Basic conversion Length Mass
16
Temperature
17
Area Length Mass
18
Volume
19
Volume Flowrate
20
Velocity
21
Pressure
22
Energy
23
Heat Flowrate and Power
24
Viscosity ความหนืดสัมบูรณ์
25
Viscosity ความหนืดเชิงจลนศาสตร์
26
Water Properties
27
GUAGE PRESSURE P guage = P absolute - P atm P guage is obtained from pressure measuring device.
28
4. BASIC FLOW IN PIPE
29
Flow Pattern LAMINAR or TURBULENCE ? Re < 2000Re > 10000
30
REYNOLDS NUMBER WATER FLOW AT 1.2 m/s IN A ½” PIPE =TURBULENT Inertia vs. Viscous Effect
31
LOSS MAJOR LOSS: LOSS IN PIPE MINOR LOSS: LOSS IN FITTINGS AND VALVES
32
LOSS IN PIPE LOSS IN PIPE CAUSED BY FRICTION BETWEEN FLUID AND PIPE SURFACE. FRICTION CAN BE RELATED TO SHEAR STRESS. A PAPA PBPB B
33
VELOCITY AND LOSS LOSS IN PIPE VARIES WITH SQUARE OF FLUID VELOCITY AB
34
FLOW AND LOSS FLUID VELOCITY IS RELATED TO THE FLOW RATE VIA PIPE SIZE THUS.. C = f (DIAMETER, ROUGHNESS)
35
FRICTION LOSS CHART DIAMETER VELOCITY DESIGN VELOCITY 1.2 TO 2.4 m/s
36
FRICTION LOSS EQUATION HAZEN-WILLIAMS EQUATION (SI UNIT) DARCY WEISBACH EQUATION READING ASSIGNMENT: 3-2 FRICTION LOSS IN PIPE
37
MOODY DIAGRAM
38
MINOR LOSS LOSS IN FITTING: USE EQUIVALENT LENGTH LOSS IN VALVE: USE C V OR K V (DISCUSS LATER)
39
5. QUICK LOOK AT PIPE DRAWINGS
40
NEXT SESSION PIPING MATERIALS AND EQUIPMENTS VALVES PUMPS
41
HOMEWORK 1 Find a water valve (in a toilet, a kitchen or the backyard). Measure inlet pipe size. Measure the flow rate from a faucet at 25%, 50%, 75% and 100% opening (in lpm). Find out the supply pressure (in m.WG.)