1 II. Bottom-up Determine secondary controlled variables and structure (configuration) of control system (pairing) A good control configuration is insensitive to parameter changes Step 5. REGULATORY CONTROL LAYER 5.1Stabilization (including level control) 5.2Local disturbance rejection (inner cascades) What more to control? (secondary variables) Step 6. SUPERVISORY CONTROL LAYER Decentralized or multivariable control (MPC)? Pairing? Step 7. OPTIMIZATION LAYER (RTO)
2
2 ”Advanced control” STEP 6. SUPERVISORY LAYER Objectives of supervisory layer: 1. Switch control structures (CV1) depending on operating region Active constraints self-optimizing variables 2. Perform “advanced” economic/coordination control tasks. –Control primary variables CV1 at setpoint using as degrees of freedom (MV): Setpoints to the regulatory layer (CV2s) ”unused” degrees of freedom (valves) –Keep an eye on stabilizing layer Avoid saturation in stabilizing layer –Feedforward from disturbances If helpful –Make use of extra inputs –Make use of extra measurements Implementation: Alternative 1: Advanced control based on ”simple elements” Alternative 2: MPC
3
3 Control configuration elements Control configuration. The restrictions imposed on the overall controller by decomposing it into a set of local controllers (subcontrollers, units, elements, blocks) with predetermined links and with a possibly predetermined design sequence where subcontrollers are designed locally. Some control configuration elements: Cascade controllers Decentralized controllers Feedforward elements Decoupling elements Selectors Split-range control
4
4 Cascade control arises when the output from one controller is the input to another. This is broader than the conventional definition of cascade control which is that the output from one controller is the reference command (setpoint) to another. In addition, in cascade control, it is usually assumed that the inner loop K2 is much faster than the outer loop K1. Feedforward elements link measured disturbances to manipulated inputs. Decoupling elements link one set of manipulated inputs (“measurements”) with another set of manipulated inputs. They are used to improve the performance of decentralized control systems, and are often viewed as feedforward elements (although this is not correct when we view the control system as a whole) where the “measured disturbance” is the manipulated input computed by another decentralized controller.
5
5 Use of extra inputs Two different cases 1.Have extra dynamic inputs (degrees of freedom) Cascade implementation: “Input resetting to ideal resting value” Example: Heat exchanger with extra bypass 2.Need several inputs to cover whole range (because primary input may saturate) (steady-state) Split-range control Example 1: Control of room temperature using AC (summer), heater (winter), fireplace (winter cold) Example 2: Pressure control using purge and inert feed (distillation)
6
6 Extra inputs, dynamically Exercise: Explain how “valve position control” fits into this framework. As en example consider a heat exchanger with bypass
7
7 QUIZ: Heat exchanger with bypass Want tight control of T hot Primary input: CW Secondary input: q B Proposed control structure? qBqB T hot closed
8
8 qBqB T hot TC Use primary input CW: TOO SLOW Alternative 1 closed
9
9 qBqB T hot TC Use “dynamic” input q B Advantage: Very fast response (no delay) Problem: q B is too small to cover whole range + has small steady-state effect Alternative 2 closed
10
10 qBqB T hot TC Alternative 3: Use both inputs (with input resetting of dynamic input) closed FC q Bs TC: Gives fast control of T hot using the “dynamic” input q B FC: Resets q B to its setpoint (IRV) (e.g. 5%) using the “primary” input CW IRV = ideal resting value
11
11 Exercise Exercise: (a)In what order would you tune the controllers? (b)Give a practical example of a process that fits into this block diagram
12
12 Too few inputs Must decide which output (CV) has the highest priority –Selectors
13
13 Use of extra measurements: Cascade control ( conventional) The reference r 2 (= setpoint y s2 ) is an output from another controller General case (“parallel cascade”) Special common case (“series cascade”) Not always helpful… y 2 must be closely related to y 1
14
14 Series cascade 1.Disturbances arising within the secondary loop (before y 2 ) are corrected by the secondary controller before they can influence the primary variable y 1 2.Phase lag existing in the secondary part of the process (G 2 ) is reduced by the secondary loop. This improves the speed of response of the primary loop. 3.Gain variations in G 2 are overcome within its own loop. Thus, use cascade control (with an extra secondary measurement y 2 ) when: The disturbance d 2 is significant and G 1 has an effective delay The plant G 2 is uncertain (varies) or nonlinear Design / tuning (see also in tuning-part): First design K 2 (“fast loop”) to deal with d 2 Then design K 1 to deal with d 1
15
15 Control of primary variables Purpose: Keep primary controlled outputs c=y 1 at optimal setpoints c s Degrees of freedom: Setpoints y 2s in reg.control layer Main structural issue: Decentralized or multivariable?
16
16 Decentralized control (single-loop controllers) Use for: Noninteracting process and no change in active constraints +Tuning may be done on-line +No or minimal model requirements +Easy to fix and change -Need to determine pairing -Performance loss compared to multivariable control - Complicated logic required for reconfiguration when active constraints move
17
17 Multivariable control (with explicit constraint handling = MPC) Use for: Interacting process and changes in active constraints +Easy handling of feedforward control +Easy handling of changing constraints no need for logic smooth transition -Requires multivariable dynamic model -Tuning may be difficult -Less transparent -“Everything goes down at the same time”
18
18 Outline Control structure design (plantwide control) A procedure for control structure design I Top Down Step 1: Degrees of freedom Step 2: Operational objectives (optimal operation) Step 3: What to control ? (self-optimizing control) Step 4: Where set production rate? II Bottom Up Step 5: Regulatory control: What more to control ? Step 6: Supervisory control Step 7: Real-time optimization Case studies
19
19 Step 7. Optimization layer (RTO) Purpose: Identify active constraints and compute optimal setpoints (to be implemented by supervisory control layer) Main structural issue: Do we need RTO? (or is process self- optimizing) RTO not needed when –Can “easily” identify change in active constraints (operating region) –For each operating region there exists self-optimizing variables
20
20 Extra For students that take PhD course!
21
21 Cascade control: y 2 not important in itself, and setpoint (r 2 ) is available for control of y 1 Decentralized control (using sequential design): y 2 important in itself Make use of extra measurements: Partial control
22
22 Partial control analysis Primary controlled variable y 1 = c (supervisory control layer) Local control of y 2 using u 2 (regulatory control layer) Setpoint y 2s : new DOF for supervisory control Assumption: Perfect control (K 2 -> 1 ) in “inner” loop Derivation: Set y 2 =y 2s -n 2 (perfect control), eliminate u 2, and solve for y 1
23
23 Partial control: Distillation Supervisory control: Primary controlled variables y 1 = c = (x D x B ) T Regulatory control: Control of y 2 =T using u 2 = L (original DOF) Setpoint y 2s = T s : new DOF for supervisory control u 1 = V
24
24 Limitations of partial control? Cascade control: Closing of secondary loops does not by itself impose new problems –Theorem 10.2 (SP, 2005). The partially controlled system [P 1 P r1 ] from [u 1 r 2 ] to y 1 has no new RHP-zeros that are not present in the open-loop system [G 11 G 12 ] from [u 1 u 2 ] to y 1 provided r 2 is available for control of y 1 K 2 has no RHP-zeros Decentralized control (sequential design): Can introduce limitations. –Avoid pairing on negative RGA for u 2 /y 2 – otherwise P u likely has a RHP- zero