Power Quality Product Overview

Similar presentations


Presentation on theme: "Power Quality Product Overview"— Presentation transcript:

1 Power Quality Product Overview
GE Consumer & Industrial

2 Content Introduction UPS Products Static Transfer Switches GE’s unique technologies

3 Energy is the Key The actual power grid was built to supply the 3 main inventions of the last Century: the light bulb the electric motor the refrigerator Utilities provide a reliability of 99,9% = 8 hours out of tolerance/year „good enough“ for this type of application To produce, store, transfer and restore 4 MB of data we „burn“ the energy equivalent of Kilo of coal

4 = Utility not meeting business requirements Process Fact: 99.9%
Need: 99, % ELECTRICAL POWER „DIGITAL WORLD“ CRITICAL RAW MATERIAL OF THE 21ST CENTURY: QUANTITY & QUALITY & RELIABILITY OF ELECTRONS

5 customized premium power solutions
Power Quality Cluster Quality & Reliability TVSS Protective Relays UPS Active Filter Switch Gear PDU Utility Feed/ Sub station STS ATS Line Cond. DC 48 /120 V PLC Drives customized premium power solutions Local Generation Ride-through Energy Storage Diesel Genset Energy Rental Battery Battery Monitoring Quantity & Availability Fuel Cell Turbine Fly wheel Super Cap

6 Key Products – GE C&I UPS Uninterruptible Power Supply Active Filters
Static Transfer Switches Protecting equipment and processes against disturbances in the utility Eliminating higher harmonic currents, mains cleaning Automatic switches to increase reliability of supply to loads

7 UPS – Product Range 0.35 – 3 KVA 3 to 30 KVA Single or Redundant
Commercial Telecom - Wireless Telecom - Wireline Small Enterprise – Data Centre Medium Enterprise – Data Centre Large Enterprise – Data Centre External Data Centre Semiconductor Fab Process Industry BioTech, Pharmaceuticals, Hospitals

8 Single Phase output UPS
Typical Application ML Series VA (Sourced) Entry level product range Line interactive pluggable Single PC EPOS CCTV cameras Match VA Mid level line interactive pluggable High reliability and performance Small server Hubs, routers NetPro Servers and PCs Small IT networks Telecom networks Process control VA Double conversion pluggable Mature technology, replacement 2006 LP Series The ML Series is for simple applications requiring a medium level of protection. Both the ML Series and the Match UPS are line interactive, so they provide voltage stabilisation but do not stabilise any frequency that may be out of tolerance coming from the mains. The main performance difference between the ML and the Match is the waveform shape when the UPS provides power from the battery. The ML gives a square shaped waveform, the Match a sinewave. Sinewave is better for more sensitive loads such as routers. The Match is one of our most reliable UPS ranges in terms of performance. Our main competitor for both the ML and the Match is APC. APC have a very wide distribution model. We are developing more channels into distribution to increase our market penetration with these products. The NetPro UPS is pluggable (like the ML and Match) but has a completely different technical design. The NetPro protects also from frequency irregularities. The NetPro marks the start of our Double Conversion – or Voltage and Frequency Independent – UPS. We sell the NetPro into both the IT and the industrial (process control for loads such as elevators, electronic doors, etc) marketplace. We also have a project running at the moment to sell this to GE Wind for their turbine applications. It‘s also approved by DNV for maritime use. Main competitors include Powerware, MGE and APC. The NetPro and the Match make very good margins. They also have an excellent warranty period of three years because of the Superior Battery Management. The LP series of UPS begins our installable ranges. The LP has some unique features that allow us to sell into some specific markets where a standard UPS (without additional filters, etc) would normally not do the job. It‘s tranformer-based, and so provides ultimate protection against disturbances. The LP Series RPA make the UPS scalable and means the customer can have an N+1 solution to protect very critical loads. Main competitors for the LP include Powerware, Liebert and MGE. 3 - 10kVA LP11/31T 8 - 20kVA LP31 Double conversion installable Unique RPA Mid-range IT networks Healthcare equipment Process control Large telecom networks

9 Three Phase output UPS Typical Application 10 - 120kVA
LP33 Series Typical Application Healthcare equipment IT infrastructure Telecom networks kVA Transformerless; Clean Input Tech Small footprint, front access SitePro kVA ; kVA Transformer base design Configurable according to installation requirements Process control Transportation infrastructure Telecom networks Healthcare equipment SG Series LP33: - The low footprint of the LP33 is best in class and provides the user with more space for other equipment. Combined with its low weight, it can be easily handled, reducing installation time and costs. (transformerless technology) - GE’s clean input Active IGBT technology provides low input harmonics feedback distortion, constant for all load levels from 20% to 100% load. This allows the user to save in the sizing of upfront UPS equipment: generator sets, cabling and circuit breakers. It also reduces the disturbance on nearby equipment without the need of additional filters.  - Input/Output terminals are easily accessible from the front, as are all other serviceable parts. True front access provides the possibility to place the unit against a wall or in a ‘back to back ‘ configuration, saving floor space for other customer equipment (for example, in a data center,…) and reducing repair time. - EMC class A filters are installed as standard (at no additional cost) in the UPS, ensuring the reduction of interference with other equipment supported in the application (telecom, broadcasting,…). This protects the quality of the customer application equipment, for example with images from a medical scanner in healthcare application. Other UPS without the EMC filters as standard can cause interference leading to a distorted image. SitePro: - Transformer technology reuired by customers... Innova healthcare project 10-20kVA and now 30kVA - Configurable: Extensive options to satify particular customers requests (eg isolation adaptation transformer for customers that have different local voltage) SG Series: - High efficiency 91% reduced customers opeartion costs and cost saving in air conditioning design (eg medical equipmet) - True front access for operation and maintennace saving space at customers site; installing against wall,;easy to handle - Load galvanic separation : Interference reducttion with other customer equipment - No voltage distortion for typical medical equipment: enhanced medical equipment productivity; improved quality of application (EG images) and reduced service intervention (~60% labor hour and spare parts reduction) kVA Best in class in output performance EMC solution for critical applications IT networks Industrial applications Broadcasting systems

10 Static Transfer Switches
K1 normally OFF U1 CT1 O2 K2 K5 normally ON O3 K4 PRIMARY SOURCE L1 L2 U2 O1 K3 SECONDARY STS OUTPUT STS Static Transfer Switch Electronic switch that ensures uninterruptible switching between a preferred source and an alternate source. (primary or secondary) Automatic operation – in case the preferred source is out of limits (fails) the load is automatically transferred to the healthy alternate source. This transfer is seamless in case both sources are synchronized

11 Static Transfer Switches
Redundant power supplies Redundant cooling Over voltage protection Front access for service Manual bypass Alarm contact interface User friendly control panel Neutral dimensioned for 200% Unique conductivity detection 3 phase STS: 25 – 630 A 400V 3&4 pole 1 phase STS: 25 – 400 A 230V 1&2 pole

12 GE‘s unique technologies
RPA Redundant Parallel Architecture High reliability UPS cluster with no single point of failure SEM Super ECO Mode Saving energy whilst maintaining high protection level IEM Intelligent Energy Management Award winning concept for energy savings

13 Redundant Parallel Architecture
utility supply Up to 8 units in parallel Any UPS able to be the logic leader Decentralized bypass Redundant Communication Bus Transparent failover and recovery process True redundancy with no single point of failure to critical load

14 VFI concept Super ECO Mode SS DC AC DC AC 2 Conversion Processes:
+ optimal protection for mission critical applications - increased energy losses Balance: For less critical loads run UPS on bypass continuously In case mains is out of limits transfer the load to inverter Super ECO Mode: not only is the load supplied on bypass, but the inverter is also switched off, increasing energy savings

15 Fast Transfer to Inverter
Super ECO Mode < 2ms Bypass on/off Output voltage Inverter current Inverter control Fast Transfer to Inverter Super ECO mode Efficiency : 98% to Inverter in case Bypass is out of limits Fast error detection Extremely short transfer times (<2 ms) User definable scheduling Available for 10 – 500 kVA

16 UPS: Cost of Ownership Intelligent Energy Management
Purchasing Cost & Installation Cost Direct Operating Cost Efficiency = Energy Losses = Heat Indirect Operating Cost Heat = air conditioning / Ventilation Maintenance Cost

17 Typical Load Situation
Intelligent Energy Management Load Typical Load Situation 100% 20% 20% Time 30% 70% Full load: 5 x 10 = 50 hours Partial load: 5 x x 24 = 188 hours

18 Intelligent Energy Management
Full-Load Condition 75 % LOAD = 100 % UPS kVA Load Time 75 % 8.00 18.00 UPS kVA LOAD 300 kVA 75 % UPS kVA Efficiency 4 UPS 75 % Load% UPS kVA

19 Partial Load Condition
Intelligent Energy Management Partial Load Condition 15 % Load UPS kVA LOAD = 20 % Time 18.00 8.00 15 % UPS kVA LOAD 60 kVA 15 % Efficiency 4 UPS UPS kVA 15 % UPS kVA Load%

20 Partial Load Condition with IEM (redundancy)
Intelligent Energy Management Partial Load Condition with IEM (redundancy) UPS kVA Load LOAD = 20 % 18.00 8.00 Time UPS kVA LOAD 60 kVA 30 % UPS kVA Efficiency 2 UPS 30 % UPS kVA Load%

21 Intelligent Energy Management
Partial Load with IEM (mains redundancy) UPS kVA Load Time LOAD = 20 % 18.00 8.00 UPS kVA LOAD 60 kVA UPS kVA Efficiency 1 UPS Load% UPS kVA 60 %

22 Intelligent Energy Management
Number of UPS : 4 Full load condition : 75% Partial Load Condition : 10% Losses : efficiency of UPS* Cost per kWh : 0.11 $ Hours at full load : 50h / week Hours at partial load : 118 / week *: Load Efficiency 75% % 50% % 30% % 15% % 10 15 20 30 40 60 80 100 120 160 200 250 330 400 500 5000 10000 15000 20000 25000 30000 35000 UPS POWER (kVA) IEM Savings with Utility redundancy IEM Savings with UPS redundancy US$