LST SAFETY FRANK O’NEILL (SLAC) 10/21/03
2
SAFETY ISSUES Seismic Fire Electrical Environmental
3
SIESMIC SAFETY ~10,000 kg of brass per sextant. Approval from Earthquake Safety Committee 10/17/03
4
FIRE SAFETY ISSUES Combustibility of LST material Flammable Component of Gas Mixture Wire and Cable Fire Safety Rating
5
LST MATERIAL COMBUSTABILITY LST extrusion is constructed of plastic (PVC) –Rated Class V-0 in accordance with UL-94 (Tests of Flammability of Plastic Materials) –Loaded with 20% Calcium Carbonate This provides the PVC with some fire retardant properties Small scale laboratory fire tests were conducted by Hughes Associates –ASTM E-1354 “cone calorimeter” test –Comparison of RPC and LST samples
6
Comparison of LST and RPC MaterialTime to Flaming (sec) Time to End of Flaming (sec) Peak HRR (kW/m 2 ) Avg HRR (kW/m 2 ) Calculated Flammability Parameter RPC-110940351.5111.51.10 RPC-210910340.1103.11.02 RPC-313857323.7118.21.17 RPC-AVG11902338.4110.91.1 LST-16593119.384.30.15 LST-26811286.459.5-0.01 LST-358103110.374.90.18 LST-AVG64103105.372.90.1
7
TEST RESULTS The PVC material exhibited significantly better ignitability and heat release rate characteristics than the existing RPC material The PVC has a strong tendency to intumesce resulting in an insulating layer that inhibits flame spread
8
GAS MIXTURE 3 components: Argon, Isobutane, and CO 2 Similar Gas Mixtures utilized on other Detectors –SLD: 2.5% Ar, 9.5% isobutane, 88% CO 2 –ZEUS: 3% Ar, 8% isobutane, 89% CO 2 Final decision on mixture pending Nonflammable mixture will be utilized Hughes Associates providing consulting services for evaluation of mixtures
9
Wire and Cable Fire Safety High Voltage Cable meets the CERN, Safety Instruction 23 Signal Cables meet the IEC 331-1 (Flame and Fire Propagation Test)
10
Electrical Safety High Voltage –Passive over-current protection in power supplies –~5500 Volts and ~1 nF ~15 mJ. –Startle hazard Low voltage –Read-out electronics in VME crates –Usual precautions such as fusing
11
ENVIRONMENTAL SAFETY Bay Area Air Quality Management District (BAAQMD) issues SLAC a permit for discharge of VOCs –SLAC may need to modify the permit –Coordination with the SLAC Environmental Protection Department is ongoing