1 ESS Cryogenic regulation loops proposal Thermal shield Power Couplers double-wall CM cool down Stand by and nominal operation CM warm up Bertrand Renard – CEA - 141205
2
2 Thermal Shield Thermal shield pressure: no CV60 open Thermal shield mass flow rate: no ECCTD only (observation, no regulation) Thermal shield outlet temperature Measurement: TT65 Redundancy: TT64 Actuator: CV61 Setpoint: 50 K (cool down and nominal)
3
3 Power Couplers double-wall PC double-wall pressure: no, CV03 open PC double-wall outlet temperature: Measurement: TT13 (or TT23…) Redundancy:TT11 (or TT21…) ECCTD only Actuator: CV11 (or CV21…) Setpoint nominal: ~150 K tbc Setpoint cool down: ~TT06 / 2 PC double-wall mass flow rate: only for redundancy Measurement: FT11 (or FT21…) Actuator: CV11 (or CV21…) Redundancy setpoint: define m = f(PC RF power) Cooling-down setpoint: m standby x (300 – TT05)/295
4
4 Power Coupler heaters PC outlet heater Measurement: TT15 (or TT25…) Actuator: EH11 (or EH21…) Setpoint: ~285 K tbc Accessible, no redundancy PC ceramic heater Measurement: TT14 (or TT24…) Actuator: EH12 (or EH22…) Setpoint: ~285 K tbc no redundancy
5
5 Accelerator cool down to 4.5 K Cryomodule pressure: CV03 and CV04 open (CV01 open) Measurement: PT03 Actuator: CV02 Setpoint: <1,5 bara no redundancy except for CTL pressure Cryomodule mass flow rate: no ECCTD only (observation, no regulation) Cryomodule inlet temperature: no Regulated by the Cryoplant
6
6 1 CM cool down to 4.5 K Cryomodule pressure: CV03 and CV06 open Measurement: PT03 Actuator: CV02 Setpoint: <1,5 bara Cryomodule mass flow rate: no Cryomodule inlet temperature: no (CV01 open); CV02 opening ramp to reduce thermal gradient
7
7 4.5 K active standby Cryomodule bath pressure: CV03 & CV04 open Measurement: PT03 Actuator: CV02 Setpoint: <1,5 bara Accessible, no redundancy Cryomodule mass flow rate: no ECCTD only (observation, no regulation) LHe bath level Measurement: LT01 Redundancy: LT02 Actuator: CV01 + CV02 Setpoint: = 25% of Phase Separator
8
8 Accelerator cool down to 2 K Cryomodule inlet pressure: no CV03 open Cryomodule inlet temperature: defined by pressure Cryomodule bath level CV02 closed ; Measurement: LT01 / LT02 Actuator: CV01 Setpoint: 25% of the Phase separator Actuator: CV04 Setpoint: >10% of the Phase separator This regulation avoids evaporation of the bath. Once 2 K is reached, CV04 opens and CV01 regulates.
9
9 Nominal operation and 2 K stdby LHe inlet pressure: no Regulated by the Cryoplant: CV03 open LHe bath pressure: no Regulated by the Cryoplant: CV04 open LHe bath temperature: no (imposed by pressure) LHe level: Measurement: LT01 Redundancy: LT02 Actuator: CV01 Setpoint: = 25% of Phase Separator
10
10 Accelerator warm up 2 to 4.5 K Cryomodule pressure: CV03 closed, (CV01 and CV02 open). CV03 closed => no PC cooling CV04 open CTL pressure ramp regulated by the Cryoplant. Measurement: LT01 / LT02 Actuator: Heaters EH30 (and EH40…) Setpoint: 50% of Phase Separator Cryomodule mass flow rate: no Cryomodule temperature: no Helium circulation may be used but beware for LHe level rise.
11
11 CM passive warm up 4.5 to 300 K Stop Thermal shield cooling Cryomodule pressure: CV03 closed, (CV01 and CV02 open). CV03 closed => no PC cooling CV06 for 1 CM warm up Cryomodule temperature Measurement: average of all cold mass T Actuator: Heaters EH30 (and EH40…) to speed up Setpoint: no
12
12 CM active warm up 4.5 to 300 K Stop Thermal shield cooling Cryomodule pressure: CV03 closed, CV01 and CV02 open. CV06 open to He recovery line Cryoplant recovery line sets pressure but overpressure must be avoided Measurement: PT03 Actuator: CV05 Setpoint: <1.2 bara Cryomodule inlet temperature Measurement: TT05 Redundancy: TT91 Actuator: CV05 Setpoint: = temperature ramp on (TT05+TT06)
13
13 Accelerator warm up 4.5 to 300 K Stop Thermal shield cooling Cryomodule pressure: CV03 closed, CV01 and CV02 open. CV04 open for full machine warm up Cryoplant sets pressure but overpressure must be avoided Measurement: PT03 Actuator: CV05 Setpoint: <1.2 bara Cryomodule inlet temperature Measurement: TT05 Redundancy: TT91 Actuator: CV05 Setpoint: = temperature ramp on (TT05+TT06)