Download presentation
Published byRosamund Benson Modified over 9 years ago
1
Lecture Objectives: Plumbing Pumps Hydronic distribution systems
Chiller/Boiler – Storage – Building Pumps Reading assignment: Chilled Water Plant Design Guide (Section 4)
2
Primary/Secondary and Tertiary Pumping (schematics A&B below)
3
Coil Pumping Strategies
Variable speed pumps vs. Single pas Valve vs. Mixing valves vs. Diverting Valves
4
Impact of Piping Coil How will this affect needed CHW flow?
What about the chiller performance?
5
Plumbing Arrangement in Building’s Hydronic Systems
Radiators Baseboard heaters Fan coil systems
6
What is the difference between these two configuration?
7
Hydronic Terms Head loss Open-loop vs. closed loop Open System
Closed System h Pump Chiller Cooling coil in AHU Pump
8
Is this open or closed system ?
Cooling towers
9
Relationship between velocity in a pipe and pressure drop
Δp ~ v2 Δp = Constant × v2 Required power (P) for the pump P = V × Δp P –power [W], V –volume flow rate [m3/s], v – velocity [m/s] Δp – pressure drop [Pa] Δp ~ v2 (Δp ~ V2 – when same pipe is used) P ~ V × V2 – when same pipe is used P ~ V P2/P1 = (V2/V1)3 For the same pipe When different pipe is used for the same flow rate: For the same flow rate V Reduction of D: smaller pipe larger pipe Δp [Pa or ft water] D1 D2= D1/2 A1 V1 P1 A2=1/22 A1 V2=22 V1 P2/P1 = (D1/D2)4 - for the same flow rate or 50% smaller diameter of the pipe for the same flow rate wee have: 4 times larger velocity 16 times larger pressure drop and 16 times lager power for the pump v [m/s or fpm]
10
Head Loss
11
Fittings
12
Pumps Raise pressure and produce flow Main type Centrifugal Example of
Turbine pump Base mounted Inline Reading (textbook) Page
13
Pump curves NPSHR = Net Positive Suction Head Required
15
Changing Pump Speed
16
Net Positive Suction Head (cavitation)
17
Curve for Multiple Pumps
18
System Curves ∆p ∆p A+B A B A+B A B V A B V A B Parallel Serial
19
Find a system curve for this plumbing configuration
20
System balancing AHU1 AHU2 HC1 HC2 100 ft 1000 ft 10 gpm 2 gpm 10 ft
pump BOILER
21
Valves Section 5-14 and 6-15 in the textbook Types Butterfly Valves
Ball Valves Globe Valves Three way valves
22
Valve Sizing and Flow Coefficient
Cv value: in liter/hour or…. in Pa Control Valve Selection For Hydronic Systems reference:
23
Control Valve Selection For Hydronic Systems
Before DC we tried to do this Valve authority
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.