HVAC – Air Handling Unit Heating Ventilating AC =Cooling HVAC – Basic Terms hQ = 200,000 Btu/h CO2 20 cfm/ pers 50 people 1000 cfm cQ assume to = 20 tr.

Similar presentations


Presentation on theme: "HVAC – Air Handling Unit Heating Ventilating AC =Cooling HVAC – Basic Terms hQ = 200,000 Btu/h CO2 20 cfm/ pers 50 people 1000 cfm cQ assume to = 20 tr."— Presentation transcript:

1

2 HVAC – Air Handling Unit Heating Ventilating AC =Cooling HVAC – Basic Terms hQ = 200,000 Btu/h CO2 20 cfm/ pers 50 people 1000 cfm cQ assume to = 20 tr = 70 ti = 62 tsi = 105 20% coil Q= V*rho*cp*TD 5000 cfm hQ vent = V*rho*cp*TD

3 HVAC – Basic Terms By Conduction Convection Radiation (Heating Load) Heat Out =Heat In (Cooling Load including “Latent Load”) Heat and Humidity in = Heat and Humidity out

4 HVAC – Basic Terms Conduction Area Temperature Resistance

5 HVAC – Basic Terms Conduction

6 Convection Radiation HVAC – Basic Terms

7 HVAC – Basic Systems Heating hQ sen + hQ vent = coilQ sen hQ sen = 200,000 Btu/h

8 HVAC – Basic Systems Heating

9 w w HVAC – Basic Systems - AC AC Water to Water

10 w A HVAC – Basic Systems - AC

11 A A

12 w A

13 Constant Volume Double Duct Terminal Box Damper blades change air flow as the pressure at the inlet to the box increases or decreases and in response to room temperature

14 Variable Volume Single Duct Terminal Box Pressure Independent (between Max and Min), based on room thermostat. If temperature rises, damper opens for more cooling. Air Flow is unaffected by other boxes in the system. 55 – 60 o P Sensor Thermostat = Master Velocity = Sub Master cfm

15 Inlet Guide Vanes

16 Variable Speed Drives

17

18

19

20 COP – dimensionless! – EER – dimensions of Btu/h/W! HVAC - Cooling ideal evQ kpH’

21 The energy efficiency rating (EER) of an air conditioner is its BTU/h rating over its Wattage. Example: window air conditioner Rating: 10,000-BTU/h Power Consumption: 1,200 watts EER = 10,000 BTU/h/1,200 watts = 8.3 Btu/Wh Normally a higher EER is accompanied by a higher price. HVAC - Cooling

22 Choice between two 10,000-BTU/h units 1. EER of 8.3, consumes 1,200 watts 2. EER of 10, consumes 1000 watts. Price difference is $100. Usage: 4 months a year, 6 hours a day. Electricity Cost: $0.10/kWh. =========================================== 4 mo. x 30 days/mo. x 6 hr/day = 720 hours (720 h x.2 kW) x $0.10/kWh = $14.40 Savings Since the EER 10 unit costs $100 more, it will take about seven years for this more expensive unit to break even HVAC - Cooling

23 Energy Analysis Example

24

25

26

27

28

29

30

31

32

33

34 ECM: Heat Recovery